Skip to product information
1 of 1

SINOFUSE RS306-01-T5Z Bolt-Connected High-Speed Fuse Series, 32–400A, AC1250V/DC1000V

Regular price $30.00 USD
Regular price Sale price $30.00 USD
Sale Sold out
Shipping calculated at checkout.
Quantity
Model

Secure checkout via Credit Cards, PayPal & Bank Wire (T/T)

Visa Mastercard PayPal Apple Pay Google Pay American Express

SINOFUSE RS306-01-T5Z is a bolt-connected high-speed fuse series for partial-range protection, covering 13 verified rated-current variants from 32A to 400A. The series is rated AC1250V under IEC requirements and DC1000V under UL requirements and uses the aR utilization category. Published breaking capacity is AC 100kA and DC 50kA with a 10ms DC time constant. All included models use M8 mounting bolts with a recommended installation torque of 11 N·m. This series page organizes the exact current-rated models, I²t characteristics and power-loss data for technical comparison, replacement review and B2B procurement.

RS306-01-T5Z Series Overview

The RS306-01-T5Z family provides rated-current options at 32A, 40A, 50A, 63A, 80A, 100A, 125A, 160A, 200A, 250A, 315A, 350A and 400A. The manufacturer references UL 248.13 and IEC 60269-4 for performance, with structure and performance specified to IEC 60269 and UL 248. RoHS, CE and UL are identified for the series. Electrical characteristics that vary by model include pre-arcing I²t, clearing I²t and power loss at 0.5In and In. Published I²t data is based on an AC1390V, 50kA test condition.

Technical Specifications

Specification Series Data
Product Type Bolt-connected high-speed fuse
Rated Voltage AC1250V (IEC) / DC1000V (UL)
Rated Current Range 32A–400A
Utilization Category aR
Breaking Capacity AC 100kA / DC 50kA, DC time constant 10ms
Performance Reference UL 248.13 / IEC 60269-4
Structure / Performance IEC 60269 / UL 248
Compliance / Certification RoHS, CE, UL
Mounting M8 mounting bolts
Recommended Installation Torque 11 N·m
I²t Test Condition AC1390V, 50kA

RS306-01-T5Z Model Selection

The RS306-01-T5Z series provides 13 verified current ratings from 32A through 400A. Select the required model according to rated current, then compare pre-arcing I²t, clearing I²t and power loss where these characteristics are relevant to the protected circuit. Confirm the AC1250V IEC or DC1000V UL requirement, aR utilization category and M8 mounting arrangement before replacement. The complete MPN should be verified before ordering because each current rating has its own published electrical characteristics.

Exact MPN Rated Current Pre-Arcing I²t Clearing I²t Loss @ 0.5In Loss @ In
RS306-01-T5Z-32A1250V 32A 73 A²s 450 A²s 2 W 10 W
RS306-01-T5Z-40A1250V 40A 138 A²s 850 A²s 2.3 W 12 W
RS306-01-T5Z-50A1250V 50A 255 A²s 1,580 A²s 2.7 W 14 W
RS306-01-T5Z-63A1250V 63A 435 A²s 2,660 A²s 3.5 W 18 W
RS306-01-T5Z-80A1250V 80A 770 A²s 4,730 A²s 4.2 W 22 W
RS306-01-T5Z-100A1250V 100A 1,250 A²s 7,620 A²s 5.4 W 28 W
RS306-01-T5Z-125A1250V 125A 2,220 A²s 13,600 A²s 6.3 W 33 W
RS306-01-T5Z-160A1250V 160A 4,200 A²s 25,600 A²s 7.6 W 40 W
RS306-01-T5Z-200A1250V 200A 6,800 A²s 42,000 A²s 9.5 W 50 W
RS306-01-T5Z-250A1250V 250A 12,500 A²s 76,500 A²s 11.5 W 60 W
RS306-01-T5Z-315A1250V 315A 25,200 A²s 155,000 A²s 13 W 68 W
RS306-01-T5Z-350A1250V 350A 35,200 A²s 216,000 A²s 14 W 73 W
RS306-01-T5Z-400A1250V 400A 50,500 A²s 309,000 A²s 15 W 82 W

Verified Applications

The RS306-01-T5Z series is specified for rail transportation, electric vehicles and marine applications. It can provide short-circuit overcurrent and backup protection for energy-storage systems, power systems, conductors and other devices and equipment. Model selection should be checked against the electrical characteristics and installation requirements of the actual protected circuit.

B2B Sourcing and Replacement Support

Apexon Supply provides B2B sourcing support for the SINOFUSE RS306-01-T5Z series, including exact-model identification and technical alignment for procurement and replacement requirements. Buyers should confirm rated current, AC/DC voltage requirements, aR category, I²t characteristics, power loss and M8 mounting requirements before replacing an existing fuse.

For RFQ review, submit the complete MPN, required quantity and application requirements. Most qualified RFQs receive a response or quote within 12 hours. This response target does not imply stock, delivery timing or product availability.

View full details